Standards | | | IEC/EN 60947, VDE 0660, CSA, UL |
Lifespan, mechanical; Coil 50/60 Hz | Operations | x 106 | 7 |
Lifespan, mechanical | Operations | x 106 | 10 |
Maximum operating frequency | | Ops./h | |
Mechanical | | Ops./h | 9000 |
Climatic proofing | | | Damp heat, constant to IEC 60068-2-78 Damp heat, cyclic to IEC 60068-2-30 |
Ambient temperature | | °C | |
Open | | °C | -25- 50 |
Enclosed | | °C | -25- 40 |
Mounting position | | | As required except vertical with terminals A1/A2 at the bottom | |
|
Mounting position | | | As required, except vertical with terminals A1/A2 at the bottom |
Mechanical shock resistance (IEC/EN 60068-2-27) | | | |
Half-sinusoidal shock, 10 ms | | | |
Basic unit without auxiliary contact module | | | |
Main contacts, make contacts | | g | 10 |
Main contacts Make/break contacts | | g | 10/8 |
Basic unit with auxiliary contact module | | | |
Main contacts make contact | | g | |
Make | | g | 10 |
Auxiliary contacts Make/break contacts | | g | 20/20 |
Protection type | | | IP20 |
Protection against direct contact when actuated from front (EN 90274) | | | Finger and back-ofhand proof |
Weight | | kg | 0.2 |
Terminal capacity of auxiliary and main contacts | | | |
Solid | | mm2 | 1 x (0.75 - 2.5) 2 x (0.75 - 2.5) |
Flexible with ferrule | | mm2 | 1 x (0.75 - 1.5) 2 x (0.75 - 1.5) |
Solid or stranded | | AWG | 18 - 14 |
Terminal screw | | | M3.5 |
Pozidriv screwdriver | | Size | 2 |
Standard screwdriver | | mm | 0.8 x 5.5 1 x 6 |
Max. tightening torque | | Nm | 1.2 |
Terminal capacity springloaded terminals main and control circuits | | | |
Solid | | mm2 | 1 x (1 - 2.5) 2 x (1 - 2.5) |
Flexible with ferrule | | mm2 | 1 x (1 - 2.5) 2 x (1 - 2.5) |
Standard screwdriver | | mm | 0.6 x 3.5 |
|
Rated impulse withstand voltage | Uimp | V AC | 6000 |
Overvoltage category/pollution degree | | | III/3 |
Rated insulation voltage | Ui | V AC | 690 |
Rated operational voltage | Ue | V AC | 690 |
Safe isolation to VDE 0106 Part 101 and Part 101/A1 | | | |
between coil and contacts | | V AC | 300 |
between the contacts | | V AC | 300 |
Making capacity (cos ϕ to IEC/EN 60947) | | A | 110 |
Breaking capacity | | | |
220/230 V | | A | 90 |
380/400 V | | A | 90 |
500 V | | A | 64 |
660/690 V | | A | 42 |
Short-circuit protection maximum fuse | | | |
Type “2” coordination | gL/gG | A | 10 |
Type “1” coordination | gL/gG | A | 20 |
|
AC-1 duty | | | |
Conventional free air thermal current, 3 pole, 50 - 60 Hz | | | |
Open | | | |
at 40 °C | Ith =Ie | A | 22 |
at 50 °C | Ith =Ie | A | 20 |
at 55 °C | Ith =Ie | A | 19 |
enclosed | Ith | A | 16 |
Notes | | | At maximum permissible ambient air temperature. |
Conventional free air thermal current, 1 pole | | | |
Notes | | | At maximum permissible ambient air temperature. |
open | Ith | A | 50 |
enclosed | Ith | A | 40 |
AC-3 duty | | | |
Rated operational current AC-3 open, 50 - 60 Hz, 3 pole | Ie | | |
Notes | | | At maximum permissible ambient air temperature. |
220/230 V | Ie | A | 6.6 |
240 V | Ie | A | 6.6 |
380/400 V | Ie | A | 6.6 |
415 V | Ie | A | 6.6 |
440V | Ie | A | 6.6 |
500 V | Ie | A | 5 |
660/690 V | Ie | A | 3.5 |
Motor rating | P | kWh | |
220/230 V | P | kW | 1.5 |
240V | P | kW | 1.8 |
380/400 V | P | kW | 3 |
415 V | P | kW | 3.1 |
440 V | P | kW | 3.3 |
500 V | P | kW | 3 |
660/690 V | P | kW | 3 |
AC-4 duty | | | |
Rated operational current AC-4 open, 50 - 60 Hz, 3 pole | Ie | | |
Notes | | | At maximum permissible ambient air temperature. |
220/230 V | Ie | A | 5 |
240 V | Ie | A | 5 |
380/400 V | Ie | A | 5 |
415 V | Ie | A | 5 |
440 V | Ie | A | 5 |
500 V | Ie | A | 3.7 |
660/690 V | Ie | A | 2.9 |
Motor rating | P | kWh | |
220/230 V | P | kW | 1.1 |
240 V | P | kW | 1.3 |
380/400 V | P | kW | 2.2 |
415 V | P | kW | 2.3 |
440 V | P | kW | 2.4 |
500 V | P | kW | 2.2 |
660/690 V | P | kW | 2.2 |
|
Rated operational current, open | Ie | | |
DC - -1 | | | |
12 V | Ie | A | 20 |
24 V | Ie | A | 20 |
60 V | Ie | A | 20 |
110 V | Ie | A | 20 |
220 V | Ie | A | 20 |
DC - 3 | | | |
12 V | Ie | A | 6 |
24 V | Ie | A | 6 |
60 V | Ie | A | 3 |
110 V | Ie | A | 2 |
DC - 5 | | | |
12 V | Ie | A | 1.8 |
24 V | Ie | A | 1.8 |
60 V | Ie | A | 1.8 |
110 V | Ie | A | 1.8 |
220 V | Ie | A | 0.2 |
Current heat losses (3- or 4-pole) | | | |
to Ith | | W | 2 |
at Ieto AC-3/400 V | | W | 0.5 |
|
Voltage tolerance | | x Uc | |
Single-voltage coil 50 Hz and dual-voltage coil 50 Hz, 60 Hz | Pick-up | x Uc | 0.8- 1.1 |
Dual-frequency coil 50/60 Hz | Pick-up | x Uc | 0.8- 1.1 |
Power consumption | | | |
AC operation | | | |
Single-voltage coil 50 Hz and dual-voltage coil 50 Hz, 60 Hz | Pick-up | VA | 25 |
Single-voltage coil 50 Hz and dual-voltage coil 50 Hz, 60 Hz | Pick-up | W | 22 |
Single-voltage coil 50 Hz and dual-voltage coil 50 Hz, 60 Hz | Sealing | VA | 4.6 |
Single-voltage coil 50 Hz and dual-voltage coil 50 Hz, 60 Hz | Sealing | W | 1.3 |
Dual-frequency coil 50/60 Hz at 50 Hz | Pick-up | VA | 30 |
Dual-frequency coil 50/60 Hz at 50 Hz | Pick-up | W | 26 |
Dual-frequency coil 50/60 Hz at 50 Hz | Sealing | VA | 5.4 |
Dual-frequency coil 50/60 Hz at 50 Hz | Sealing | W | 1.6 |
Dual-frequency coil 50/60 Hz at 60 Hz | Pick-up | VA | 29 |
Dual-frequency coil 50/60 Hz at 60 Hz | Pick-up | W | 24 |
Dual-frequency coil 50/60 Hz at 60 Hz | Sealing | VA | 3.9 |
Dual-frequency coil 50/60 Hz at 60 Hz | Sealing | W | 1.1 |
DC operation | | | |
Notes | | | Smoothed DC voltage or three-phase bridge rectifier |
Duty factor | | % DF | 100 |
Switching times at 100 % Uc | | | |
Make contact | | ms | |
Closing delay | | ms | |
Closing delay min. | | ms | 14 |
Closing delay max. | | ms | 21 |
Opening delay | | ms | |
Opening delay min. | | ms | 8 |
Opening delay max. | | ms | 18 |
Closing delay with top mounting auxiliary contact | | ms | max. 45 |
Reversing contactors | | | |
Changeover time at 110 % Uc | | ms | |
Changeover time min. | | ms | 16 |
Changeover time max. | | ms | 21 |
Arcing time at 690 V AC | | ms | max. 12 |
|
Positive operating contacts to ZH 1/457, including auxiliary contact module | | | Yes |
Rated impulse withstand voltage | Uimp | V AC | 6000 |
Rated insulation voltage | Ui | V AC | 690 |
Rated operational voltage | Ue | V | |
Rated operational voltage | Ue | V AC | 600 |
Safe isolation to VDE 0106 Part 101 and Part 101/A1 | | | |
between coil and auxiliary contacts | | V AC | 300 |
between the auxiliary contacts | | V AC | 300 |
Rated operational current | Ie | A | |
AC-15 | | | |
220/240 V | Ie | A | 6 |
380/415 V | Ie | A | 3 |
500 V | Ie | A | 1.5 |
DC-13 | | | |
Contacts in series: | | A | |
1 | 24 V | A | 2.5 |
2 | 60 V | A | 2.5 |
3 | 100 V | A | 1.5 |
3 | 220 V | A | 0.5 |
Control circuit reliability (at Ue= 24 V DC, Umin= 17 V, I min= 5.4 mA) | Failure rate | λ | <10-8, < one failure at 100 million operations |
Component lifespan at Ue= 240 V | | | |
AC-15 | Operations | x 106 | 0.2 |
DC-13 | | | |
L/R = 50 ms: 2 contacts in series at Ie= 0.5 A | Operations | x 106 | 0.15 |
Notes | | | Switch-on and switch-off conditions based on DC-13, time constant as specified |
Short-circuit rating without welding | | | |
Maximum overcurrent protective device | | | |
Short-circuit protection only | | | PKZM0-4 |
Short-circuit protection maximum fuse | | | |
500 V | | A gG/gL | 6 |
500 V | | A fast | 10 |
Current heat loss at Ith | | | |
Per contact | | W | 0.2 |