Stycznik pomocniczy AC; 2Z2R DILER-22(230V50HZ,240V60HZ)

  • szt.
  • Cena brutto: 379,21 zł 308,30 zł

Stycznik pomocniczy AC; 2Z2R DILER-22(230V50HZ,240V60HZ)

Program
Product range
    DILER Mini-contactors
Application
    Contactor relays
Connection technique
    Screw terminals
Rated operational current
     
AC-15
     
220 V
230 V
240 V
Ie A 6
380 V
400 V
415 V
Ie A 3
Conv. thermal current
Ith A 10
Contacts
     
N/O = Normally open
    2 N/O
N/C = Normally closed
    2 N/C
Contact sequence
   
For use with
    …DILE
Actuating voltage
    230 V 50 Hz, 240 V 60 Hz
Voltage AC/DC
    AC operation
Code number and version of combination
     
Distinctive number
    22E
Auxiliary contact module
Interlocked opposing contacts   22E Conforms to EN 50011 - terminal markings of the coil according to EN 50005
Interlocked opposing contacts 02DILE 24 EN 50005
Interlocked opposing contacts 04DILE 26 EN 50005
Interlocked opposing contacts 11DILE 33 EN 50005
1 early-make contact, 1 late-break contact 11DDILE 33 EN 50005
Interlocked opposing contacts 13DILE 35 EN 50005
Interlocked opposing contacts 20DILE 42 EN 50005
Interlocked opposing contacts 22DILE 44 EN 50005
1 early-make contact, 1 late-break contact 22DDILE 44 EN 50005
Interlocked opposing contacts 31DILE 53 EN 50005
Interlocked opposing contacts 40DILE 62 EN 50005
InstructionsContact numbers to EN 50011
Coil terminal markings to EN 50005
Approbationen
Product Standards IEC/EN 60947-4-1; UL 508; CSA-C22.2 No. 14-05; CE marking
UL File No. E29184
UL CCN NKCR
CSA File No. 012528
CSA Class No. 3211-03
NA Certification UL Listed, CSA certified
 
General
Standards
    IEC/EN 60947, VDE 0660, UL, CSA
Lifespan, mechanical
     
AC operated
Operations x 106 10
DC operated
Operations x 106 20
Maximum operating frequency
  Ops./h  
Maximum operating frequency
Operations/h   9000
Climatic proofing
    Damp heat, constant to IEC 60068-2-78
Damp heat, cyclic to IEC 60068-2-30
Climatic proofing
    Damp heat, constant, to IEC 60068-2-78; Damp heat, cyclical, to IEC 60068-2-30
Ambient temperature
  °C  
Open
  °C -25- 50
Enclosed
  °C -25- 40
Mounting position
     
Mounting position
    As required, except vertical with terminals A1/A2 at the bottom
Mechanical shock resistance (IEC/EN 60068-2-27)
     
Half-sinusoidal shock, 10 ms
     
Basic unit with auxiliary contact module
  g  
N/O contact
  g 10
N/C contact
  g 8
Protection type
    IP20
Protection against direct contact when actuated from front (EN 90274)
    Finger and back-of-hand proof
Weight
     
AC operated
  kg 0.17
DC operated
  kg 0.2
Terminal capacities
  mm2  
Screw terminals
     
Solid
  mm2 1 x (0.75 - 2.5)
2 x (0.75 - 2.5)
Flexible with ferrule
  mm2 1 x (0.75 - 1.5)
2 x (0.75 - 1.5)
Solid or stranded
  AWG 18 - 14
Terminal screw
    M3.5
Pozidriv screwdriver
  Size 2
Standard screwdriver
  mm 0.8 x 5.5
1 x 6
Max. tightening torque
  Nm 1.2
Spring-loaded terminals
     
Solid
  mm2 1 x (1 - 2.5)
2 x (1 - 2.5)
Flexible with or without ferrule DIN 46228
  mm2 1 x (1 - 2.5)
2 x (1 - 2.5)
Solid or stranded
  AWG 1 x (16 - 14)
2 x (16 - 14)
Standard screwdriver
  mm 0.6 x 3.5
Contacts
Positive operating contacts to ZH 1/457, including auxiliary contact module
    Yes
Rated impulse withstand voltage
Uimp V AC 6000
Overvoltage category/pollution degree
    III/3
Rated insulation voltage
Ui V AC 690
Rated operational voltage
Ue V AC 600
Safe isolation to VDE 0106 Part 101 and Part 101/A1
     
between coil and auxiliary contacts
  V AC 300
between the auxiliary contacts
  V AC 300
Rated operational current
Ie A  
AC-15
     
220/240 V
Ie A 6
380/415 V
Ie A 3
500 V
Ie A 1.5
DC-13
     
DC-13 L/R - 15 ms
     
Contacts in series:
  A  
1
24 V A 2.5
2
60 V A 2.5
3
110 V A 1.5
3
220 V A 0.5
Control circuit reliability (at Ue= 24 V DC, Umin= 17 V, I min= 5.4 mA)
Failure rate λ <10-8, < one failure at 100 million operations
Conv. thermal current
Ith A 10
Short-circuit rating without welding
     
Maximum overcurrent protective device
     
220/240 V
  PKZM0 4
380/415 V
  PKZM0 4
Short-circuit protection maximum fuse
     
500 V
  A gG/gL 6
500 V
  A fast 10
Current heat loss at Ith
     
AC operated
  W 0.2
DC operated
  W 0.3
Magnet systems
Voltage tolerance
  x Uc  
AC operated
  x Uc  
Single-voltage coil 50 Hz and dual-voltage coil 50 Hz, 60 Hz
Pick-up x Uc 0.8- 1.1
Dual-frequency coil 50/60 Hz
Pick-up x Uc 0.85- 1.1
DC operated
  x Uc  
Pick-up voltage
Pick-up x Uc 0.85- 1.3
at 24 V: without auxiliary contact component (40 °C)
Pick-up x Uc 0.7- 1.3
Power consumption
     
50 Hz
Pick-up VA 25
50 Hz
Sealing VA 4.6
50 Hz
Sealing W 1.3
60 Hz
Pick-up VA 25
60 Hz
Sealing VA 4.6
60 Hz
Sealing W 1.3
50/60 Hz
Pick-up VA 30
29
50/60 Hz
Sealing VA 5.4
3.9
50/60 Hz
Sealing W 1.6
1.1
DC operated
Pull-in = sealing W 2.6
Duty factor
  % DF 100
Switching times at 100 % Uc(approximate values)
     
AC operated closing delay
  ms 14- 21
AC operated N/O contact opening delay
  ms 8- 18
AC operated With auxiliary contact module Max. closing delay
  ms 45
DC operated closing delay
  ms 26- 35
DC operated N/O contact opening delay
  ms 15- 25
DC operated With auxiliary contact module Max. closing delay
  ms 70
Notes
Notes Making and breaking conditions to DC-13, time constant as stated
See transparent overlay "Fuses" for time/current characteristics (please enquire)
Use only equal cross-sections
Technical data according to ETIM 4.0
Connection type main circuit
    Screw connection
Rated control voltage Us at DC
  V 0
Rated control voltage Us at AC 60HZ
  V 240
Rated control voltage Us at AC 50HZ
  V 230
Number of auxiliary contacts as changeover contacts
    0
Rated operation current Ie , 400 V
  A 3
Number of auxiliary contacts as N/Cs
    2
Number of auxiliary contacts as N/Os
    2
Voltage type for actuation
    AC
Number of auxiliary contacts as N/Os, leading
    0
Number of auxiliary contacts as N/Cs, delayed switching
    0
Characteristics
1: Suppressor
2: Auxiliary contact module
Component lifespan (operations)
Ie = Rated operational current
Dimensions
DILER-…
DILER-…-G
DILER-… + …DILE
DILER-…-G + …DILE

Opis pochodzi ze strony www.moeller.net .