EASY200-POW - Zasilacz stabilizowany 24VDC,0,2A 1-faz.
- szt.
- Rabat: -178,28 zł (40 %)
- (Rabat brutto: -219,28 zł (40 %))
- Cena brutto: 328,93 zł / szt. 267,42 zł / szt.
Zasilacz stabilizowany 24VDC,0,2A 1-faz.regul. EASY200-POW
Program
Range | Switched-mode power supply units easyPOW | ||
Basic function | Accessories for remote monitoring unit PSU | ||
primary chopper controlled | |||
Phases | Single phase | ||
Input voltage range | 85 - 264 V AC | ||
Nominal input voltage | 100 - 240 V AC | ||
Rated output voltage | 24 V DC (± 3%) 12 V DC (± 4%) | ||
Measuring output current | CSA | 0.35 0.02 | |
For use with | easy500 easy700 easy800 MFD-CP8 EC4P ES4P |
Approbationen
|
General | |||
Standards | EN 55011, EN 55022, IEC/EN 61000-4, IEC 60068-2-6, IEC 60068-2-27, EN 61000-6-2 | ||
Dimensions (W x H x D) | mm | 35.5 x 90 x 58 (2 space units) | |
Weight | kg | 0.1 | |
Mounting | Top-hat rail IEC/EN 60715, 35 mm or screw fixing using fixing brackets ZB4-101-GF1 (accessories) | ||
Terminal capacities | |||
Solid | mm2 | 0.2/4 (AWG 22 - 12) | |
Flexible with ferrule | mm2 | 0.2/2.5 (AWG 22 - 12) | |
Standard screwdriver | mm | 3.5 x 0.8 | |
Max. tightening torque | Nm | 0.6 | |
Climatic environmental conditions | |||
Operating ambient temperature | °C | -25 … 55, low temperatures to IEC 60068-2-1, high temperatures to IEC 60068-2-2 | |
Condensation | Take appropriate measures to prevent condensation | ||
Storage | °C | -40- 70 | |
Relative humidity, non-condensing (IEC/EN 60068-2-30) | % | 5- 95 | |
Air pressure (operation) | hPa | 795- 1080 | |
Max. installation altitude above sea level, observe derating with higher altitudes | m | 2000 | |
Ambient conditions, mechanical | |||
Protection type (IEC/EN 60529, EN50178, VBG 4) | IP20 | ||
Vibrations (IEC/EN 60068-2-6) | Hz | ||
Constant amplitude 0.15 mm | Hz | 10- 57 | |
Constant acceleration 2 g | Hz | 57- 150 | |
Mechanical shock resistance (IEC/EN 60068-2-27) semi-sinusoidal 15 g/11 ms | Impacts | 18 | |
Drop to IEC/EN 60068-2-31 | Drop height | mm | 50 |
Free fall, packaged (IEC/EN 60068-2-32) | m | 1 | |
Mounting position | Vertical or horizontal | ||
Electromagnetic compatibility (EMC) | |||
Electrostatic discharge (IEC/EN 61000-4-2, Level 3, ESD) | kV | ||
Air discharge | kV | 8 | |
Contact discharge | kV | 6 | |
Electromagnetic fields (RFI), to IEC EN 61000-4-2 | V/m | 10 | |
Radio interference suppression | EN 55011 Class B; EN 55022 Class B, EN 50081-2 Class B | ||
Burst pulses (IEC/EN 61000-4-4, level 3) | kV | 2 | |
Power pulses (surge) (IEC/EN 61000-4-5) | kV | 2 (supply cables, symmetrical) | |
High-energy pulses (surge) (IEC/EN 61000-4-5, level 2), 24 V | kV | 0.5 (outgoer cables symmetrical, EASY…DC) | |
Radiated RFI (IEC/EN 61000-4-6) | V | 10 | |
Surge voltage (EN 50178), 24 V | kV | 6 | |
Insulation resistance | |||
Clearance in air and creepage distances | EN 50178 | ||
Insulation resistance | EN 50178 | ||
Protection class Uoutto Uin | Class II to IEC 60536 | ||
Potential isolation primary/secondary | Yes, SELV (VDE 0100 Part 410; IEC 60364-4-41, HD 384.4.41 S2) EN 60950, EN 50178 | ||
Input voltage | |||
Rated input voltage AC | V | 100/120/230/240 (-15/+10 %) | |
Protective switches AC | FAZ-C1/1 or FAZ-B6/1 | ||
Rated input voltage DC | V | 85- 264 | |
DC protective switches | FAZ-C2/1-DC | ||
Voltage range | V AC | 85- 264 | |
Frequency range | Hz | 47- 63 | |
Mains failure bridging 115/230 V (IEC/EN 61000-4-11) | ms | > 10/> 20 | |
Fuse 115/230 V | A | 1.5 slow | |
Rating data | |||
Efficiency | % | > 80 | |
Power consumption | W | Normally 7 | |
Power loss | W | Normally 1 | |
Input current | |||
Input current rated value 115/230 V AC | A | Approx. 0.17/0.05 | |
Inrush current at 25 °C 230 V | A | < 5 | |
Output voltage | |||
12 V DC (reference voltage) | |||
Rated value | V DC | 12 | |
Tolerance | % | ± 4 | |
Switching peaks | mVSS | < 7 | |
Effect of input voltage | % | ± 1 | |
Effect with 25 - 100 % load change | % | ± 1 | |
24 V DC | |||
Rated value | V DC | 24 | |
Tolerance | % | ± 3 | |
Switching peaks 115/230 | mVPP | < 50/30 | |
Effect of input voltage | % | ± 1 | |
Effect with 25 - 100 % load change | % | ± 1 | |
Output current | |||
12 V DC (reference voltage) | |||
Output current | mA | 0 - 20 | |
Effectiveness of current limitation | mA | 20 | |
Reduction of output voltage after current limitation | V | < 12 | |
Overload proof | Yes, by current limitation permanently short-circuit proof | ||
Proof against sustained short circuit | Yes | ||
24 V DC | |||
Output current | A | 0 - 0.35 | |
Effectiveness of current limitation | A | > 0.4 | |
Overload proof | Yes, by current limitation | ||
Proof against sustained short circuit | Yes, hickup-mode | ||
Special load conditions | |||
Lamp load, cold, 24 V DC | W | 2 | |
Base load present | W | 1 | |
Behaviour on emergency-stop in 24 V circuit, disconnection with contactor (contactor load, no damage) | W | 6 | |
Displays | |||
Indication of output voltage (LED, continuous green light = OK) | V DC | 24 |
Technical data according to ETIM 4.0
Type of voltage (input voltage) | AC | ||
Depth | mm | 60 | |
Height | mm | 90 | |
Width | mm | 32 |
Additional product information (links)
Opis pochodzi ze strony www.moeller.net .